Q&A
HOME
Question
ALL
1.What is the main function of a VFD? Why do industrial equipment need to use VFDs?+
A Variable Frequency Drive (VFD) is a power electronics device used to control the speed and torque of an AC motor. Its main function is to adjust the AC motor's speed and output torque so the equipment can operate according to actual demand. Through variable frequency control, it can achieve energy-saving operation, reduce mechanical shock, improve system stability, and extend equipment lifespan. In pumps, fans, conveying equipment, and various industrial automation systems, VFDs can effectively improve production efficiency and reduce electricity costs.
2.Can VFDs save energy? What is the energy-saving principle and application of VFDs in pump and fan systems?+
VFDs can effectively achieve energy-saving effects by adjusting the motor speed to make the equipment operation match the actual load demand, avoiding the energy waste caused by long-term full-speed operation.
In fluid systems such as pumps, fans, and water or oil supply equipment, if only constant-speed motors are used for quantitative supply, the flow rate cannot be adjusted according to demand, which easily causes energy waste. After installing a VFD, the motor speed and supply volume can be adjusted according to actual demand, balancing system supply and demand and improving overall efficiency.
In addition, VFDs have a soft-start function, which can reduce starting current and mechanical shock; if paired with a DC reactor (DCL) or AC reactor (ACL), the power factor can be improved to about 0.9–0.95. Therefore, VFDs are widely used in pumps, fans, compressors, conveying equipment, and various automation equipment, which not only improves control accuracy but also effectively reduces energy consumption.
In fluid systems such as pumps, fans, and water or oil supply equipment, if only constant-speed motors are used for quantitative supply, the flow rate cannot be adjusted according to demand, which easily causes energy waste. After installing a VFD, the motor speed and supply volume can be adjusted according to actual demand, balancing system supply and demand and improving overall efficiency.
In addition, VFDs have a soft-start function, which can reduce starting current and mechanical shock; if paired with a DC reactor (DCL) or AC reactor (ACL), the power factor can be improved to about 0.9–0.95. Therefore, VFDs are widely used in pumps, fans, compressors, conveying equipment, and various automation equipment, which not only improves control accuracy but also effectively reduces energy consumption.
3.How do I choose a suitable VFD? What factors need to be considered for VFD selection?+
When choosing a suitable VFD, the actual load current should be the main basis, not just the motor horsepower. During selection, factors such as the motor's rated horsepower, the proportion of long-term high load current, maximum peak current, ambient temperature, and carrier frequency requirements must be comprehensively considered. It is generally recommended to reserve a capacity margin of at least 15% above the rated current for the VFD to ensure long-term stable system operation.
Factors to consider for selection are as follows:
Factors to consider for selection are as follows:
- Variable torque load (ND normal duty): For centrifugal equipment such as fans, pumps, water pumps, and oil pumps, the load current will drop when decelerating. You can select based on the ND (Normal Duty) 120% overload capacity and choose a VFD with a rated output current greater than the motor's maximum load current.
- Constant torque load (HD heavy duty): For equipment such as air compressors, conveyor belts, mixers, and extruders, the load current does not change much in the variable frequency operation range. It is recommended to choose a VFD with HD (Heavy Duty) 150% overload capacity.
- Instantaneous large current load: If the equipment has rapid acceleration/deceleration, heavy load starting, or high inertia load, when the required current exceeds the HD 150% overload capacity, the VFD capacity should be increased.
- High carrier frequency application: If the carrier frequency is set higher than 7.5kHz, the heat generated by the VFD will increase, and it is recommended to increase the VFD capacity.
- High-temperature environment use: If the VFD is installed in a high-temperature environment or a closed control box, the capacity selection should be appropriately enlarged to avoid derated operation due to temperature rise.
4.How is a VFD installed? What precautions are needed when installing a VFD?+
When installing a VFD, ensure the equipment is installed in a well-ventilated location with an appropriate ambient temperature to avoid overheating. Power lines and control lines need to be routed separately and reliably grounded to reduce electromagnetic interference. In addition, installation should follow the product manual for wiring and settings, and confirm that the input voltage matches the motor specifications.
5.Can a single-phase induction motor be equipped with a VFD? Can single-phase motors use VFDs for speed control?+
General household single-phase water pumps and fans mostly use capacitor-start or capacitor-run single-phase induction motors, which rely on capacitors to assist in starting and running. Since the VFD output voltage is a PWM waveform containing many harmonic components, it easily causes the internal capacitors of single-phase motors to overheat, and may even cause damage to the capacitors or motor insulation.
Therefore, it is generally not recommended to add a VFD to a single-phase induction motor. If the equipment requires a VFD for speed control, it is recommended to replace the single-phase motor with a three-phase motor and then pair it with a VFD for speed control to ensure stable and safe equipment operation.
Therefore, it is generally not recommended to add a VFD to a single-phase induction motor. If the equipment requires a VFD for speed control, it is recommended to replace the single-phase motor with a three-phase motor and then pair it with a VFD for speed control to ensure stable and safe equipment operation.
6.Can a three-phase power series VFD be driven by a single-phase power supply? What should be noted when using a single-phase power supply for a three-phase VFD?+
It is usually not recommended to use a single-phase power supply to drive a three-phase power series VFD (non-standard single-phase input VFD). Three-phase VFDs are designed for three-phase power input; if a single-phase power supply is used directly, it may cause excessive rectifying current, VFD overheating, or protection actions.
If a single-phase power supply must be used under special circumstances, first check the rated current on the motor nameplate and use 2 times the motor's rated current as the reference value for selecting the VFD. The rated output current of the selected VFD must be greater than or equal to this reference value to ensure safe equipment operation.
Calculation formula: VFD rated output current ≥ Motor rated current × 2
If a single-phase power supply must be used under special circumstances, first check the rated current on the motor nameplate and use 2 times the motor's rated current as the reference value for selecting the VFD. The rated output current of the selected VFD must be greater than or equal to this reference value to ensure safe equipment operation.
Calculation formula: VFD rated output current ≥ Motor rated current × 2
7.Can general 50/60Hz standard induction motors run at over-frequency using a VFD? What should be noted for over-frequency use?+
General 50/60Hz standard induction motors can be operated over-frequency through a VFD, but it is necessary to understand their operating characteristics and limitations. When the motor operates below the rated frequency (50Hz or 60Hz), it is usually in the constant torque region; when the frequency exceeds the rated frequency, the motor enters the constant power region. In the constant power region, as the speed increases, the torque the motor can output gradually decreases, so the higher the over-frequency speed, the smaller the available torque.
Therefore, in over-frequency applications, it must be confirmed whether the motor torque after over-frequency is sufficient to drive the actual load, to avoid the equipment failing to operate normally or efficiency dropping due to insufficient torque. Generally, for most applications, a 50/60Hz standard induction motor paired with a VFD for over-frequency operation will be controlled within roughly 2 times the rated speed.
Common over-frequency applications mostly belong to equipment requiring low load and high speed, such as grinding processing machines, milling machines, and drilling machines. By using a VFD to control the motor running at higher speeds, processing efficiency can be improved and finer processing quality can be obtained.
Therefore, in over-frequency applications, it must be confirmed whether the motor torque after over-frequency is sufficient to drive the actual load, to avoid the equipment failing to operate normally or efficiency dropping due to insufficient torque. Generally, for most applications, a 50/60Hz standard induction motor paired with a VFD for over-frequency operation will be controlled within roughly 2 times the rated speed.
Common over-frequency applications mostly belong to equipment requiring low load and high speed, such as grinding processing machines, milling machines, and drilling machines. By using a VFD to control the motor running at higher speeds, processing efficiency can be improved and finer processing quality can be obtained.
8.Can a general 50/60Hz standard motor use a VFD for deceleration control? What should be noted for low-speed operation?+
Most general 50/60Hz standard induction motors can be paired with a VFD for deceleration control, but attention must be paid to the motor's insulation class and heat dissipation capacity. General standard motors mostly have Class E insulation (maximum allowable temperature about 120°C), whose temperature resistance is lower than the Class F or H insulation (155°C / 180°C) of inverter-duty motors.
In addition, standard motors usually use shaft-coupled cooling fans. When the VFD controls the motor to run at low speed, the fan speed also decreases, and the cooling capacity drops accordingly. Therefore, special attention must be paid to the load current and motor temperature rise during low-speed operation to avoid motor overheating or insulation damage caused by insufficient cooling.
Application precautions for different load types are as follows:
When using VFD control, overload protection parameters and the minimum operating frequency should also be set according to the motor's rated current to ensure the motor operates under safe conditions. Generally speaking, motors below Class E insulation are not recommended for VFD control.
In addition, standard motors usually use shaft-coupled cooling fans. When the VFD controls the motor to run at low speed, the fan speed also decreases, and the cooling capacity drops accordingly. Therefore, special attention must be paid to the load current and motor temperature rise during low-speed operation to avoid motor overheating or insulation damage caused by insufficient cooling.
Application precautions for different load types are as follows:
- Variable torque load: For equipment such as fans, blowers, and water pumps, the load current will also drop when decelerating, which is usually suitable for direct VFD control of general 50/60Hz standard motors.
- Constant torque load: For equipment such as air compressors and extruders, if long-term low-speed and high-load operation is required, it is recommended to add an independent cooling fan to the motor to improve heat dissipation capacity.
When using VFD control, overload protection parameters and the minimum operating frequency should also be set according to the motor's rated current to ensure the motor operates under safe conditions. Generally speaking, motors below Class E insulation are not recommended for VFD control.
9.Can the VFD three-phase output current be measured with a general current clamp meter?+
General handheld current clamp meters are mostly designed to measure the 50/60Hz mains frequency. If used directly to measure the VFD three-phase output current, the measurement result may be inaccurate. If a general current clamp meter must be used, it is recommended to measure within the VFD output frequency range of about 47–63Hz; the value will be relatively closer to the actual current.
Since the VFD output current contains PWM modulation and harmonic components, if a more accurate measurement result is needed, it is recommended to use a True RMS current clamp meter. A True RMS clamp meter can more accurately measure the effective value of currents containing harmonics, making it more suitable for measuring VFD output currents.
Since the VFD output current contains PWM modulation and harmonic components, if a more accurate measurement result is needed, it is recommended to use a True RMS current clamp meter. A True RMS clamp meter can more accurately measure the effective value of currents containing harmonics, making it more suitable for measuring VFD output currents.
10.Can the VFD secondary output voltage be measured with a general multimeter?+
General multimeters cannot accurately measure the VFD output voltage.
The VFD output contains high-frequency and harmonic components of PWM waves, which requires measuring with a multimeter that has both "True RMS" and "Low Pass Filter (LPF)" functions simultaneously.
The VFD output contains high-frequency and harmonic components of PWM waves, which requires measuring with a multimeter that has both "True RMS" and "Low Pass Filter (LPF)" functions simultaneously.
11.Can the VFD output be used as an AC power supply?+
The actual voltage output by a VFD is a PWM (Pulse Width Modulation) pulse voltage generated by high-speed switching of DC voltage, which then forms a nearly sine wave current through the motor's inductance characteristics. Therefore, the VFD output waveform is different from the pure sine wave AC of mains electricity and contains more voltage harmonic components.
Since the VFD output voltage is primarily designed for motor control, it is not suitable to be used as a general AC power supply. If the VFD output terminal directly supplies power to general instruments or electrical equipment, it may cause equipment abnormality or even damage due to unsuitable harmonic voltages or waveforms. Therefore, the VFD output terminal is only suitable for driving motors and must not be used as a general AC power supply.
Since the VFD output voltage is primarily designed for motor control, it is not suitable to be used as a general AC power supply. If the VFD output terminal directly supplies power to general instruments or electrical equipment, it may cause equipment abnormality or even damage due to unsuitable harmonic voltages or waveforms. Therefore, the VFD output terminal is only suitable for driving motors and must not be used as a general AC power supply.
12.Under what circumstances does a VFD need to install an ACL input reactor? What is the function of installing an ACL at the front end of a VFD?+
An ACL (input reactor) installed at the input terminal of a VFD can increase power supply impedance, suppress the impact of external surge voltage on the VFD, while also reducing the harmonic current generated by the VFD and improving the power factor, which helps to improve power quality and protect the VFD.
The following situations generally recommend or require installing an ACL input reactor at the VFD front end:
Properly installing an ACL input reactor can effectively protect the VFD, reduce harmonic interference, and improve power quality; it is one of the common and important accessories for VFD systems.
The following situations generally recommend or require installing an ACL input reactor at the VFD front end:
- When the power supply capacity is too large: When the power supply capacity exceeds 500kVA, or the power supply capacity is more than 10 times the VFD rated capacity, it is recommended to install an ACL to avoid power surge currents affecting the VFD.
- When interfering equipment exists in the power system: If there is equipment such as heaters, high-frequency devices, or welding machines in the same power system, which may generate harmonic current interference, an ACL needs to be installed at the VFD input terminal.
- When using large-capacity VFDs: Large VFDs are prone to generating higher harmonic currents during operation, which may affect power quality. Generally, an ACL or DCL needs to be installed at the input terminal to suppress harmonics and stabilize the power supply.
Properly installing an ACL input reactor can effectively protect the VFD, reduce harmonic interference, and improve power quality; it is one of the common and important accessories for VFD systems.
13.Why is the input current smaller than the output current when the VFD controls the motor operating at medium and low speeds?+
When the VFD controls the motor operating at medium and low speeds, there is often a situation where the primary-side input current is smaller than the secondary-side output current. The main reason is that the VFD simultaneously adjusts the output frequency and output voltage to control the motor speed, while the input-side power supply is mains power with fixed frequency and fixed voltage.
According to the three-phase electrical power formula:
P = √3 × V × I × COSθ
Ignoring the difference in VFD efficiency loss and power factor, the VFD input power and output power are roughly the same. Because the input side of the VFD uses a relatively high and fixed mains voltage, during medium and low-speed operation, the voltage the VFD outputs to the motor drops as the frequency decreases.
Therefore, with the power being nearly the same, because the input voltage is greater than the output voltage, the current required on the input side will be smaller; while the output side needs a larger current to maintain the same power, thus the phenomenon of the VFD input current being smaller than the output current appears.
According to the three-phase electrical power formula:
P = √3 × V × I × COSθ
Ignoring the difference in VFD efficiency loss and power factor, the VFD input power and output power are roughly the same. Because the input side of the VFD uses a relatively high and fixed mains voltage, during medium and low-speed operation, the voltage the VFD outputs to the motor drops as the frequency decreases.
Therefore, with the power being nearly the same, because the input voltage is greater than the output voltage, the current required on the input side will be smaller; while the output side needs a larger current to maintain the same power, thus the phenomenon of the VFD input current being smaller than the output current appears.
14.When a VFD controls a motor, what should be noted if the cable length exceeds 30 meters? How to protect motor insulation with long-distance motor cables?+
When a VFD controls a motor, if the motor cable length exceeds 30 meters, you need to note that the dV/dt voltage rise rate of the VFD output may affect the motor insulation. It is generally recommended to install an Output Reactor at the VFD output terminal to reduce the voltage rise rate and protect motor insulation, and it is also recommended to set the VFD carrier frequency below 2.5–5 kHz.
If the motor cable length exceeds 200 meters (such as long-distance equipment like hot spring deep well pumps), it is recommended to install a Sine Wave Filter at the VFD output terminal to convert the PWM output waveform into a near sine wave voltage, so as to reduce surge voltage and avoid motor insulation degradation, ensuring long-term stable equipment operation.
If the motor cable length exceeds 200 meters (such as long-distance equipment like hot spring deep well pumps), it is recommended to install a Sine Wave Filter at the VFD output terminal to convert the PWM output waveform into a near sine wave voltage, so as to reduce surge voltage and avoid motor insulation degradation, ensuring long-term stable equipment operation.
15.Should the carrier frequency be set high or low when using a VFD? What impact does the carrier frequency have on the VFD and motor?+
The VFD output voltage uses a PWM (Pulse Width Modulation) method, forming pulse voltage by high-speed switching of DC voltage. The higher the carrier frequency, the more pulses per output cycle, which makes the motor current waveform smoother and reduces electromagnetic noise; but at the same time, it increases IGBT switching loss, leading to increased VFD heating.
If the equipment needs long-term high-load operation or the ambient temperature is high, it is not recommended to set the carrier frequency too high; if high carrier frequency must be used, it should be set according to the carrier frequency derating current limit of the VFD specifications.
In general factory environments, it is mostly recommended to use a lower carrier frequency, which can reduce electromagnetic interference, leakage current, and surge voltage, decrease motor bearing discharge and insulation stress, while also lowering VFD heat generation and improving system stability and equipment lifespan.
If the equipment needs long-term high-load operation or the ambient temperature is high, it is not recommended to set the carrier frequency too high; if high carrier frequency must be used, it should be set according to the carrier frequency derating current limit of the VFD specifications.
In general factory environments, it is mostly recommended to use a lower carrier frequency, which can reduce electromagnetic interference, leakage current, and surge voltage, decrease motor bearing discharge and insulation stress, while also lowering VFD heat generation and improving system stability and equipment lifespan.
16.How far can the VFD LED operation panel be externally extended? What is the maximum extension distance for the RM6G1/RM6G1e operation panel?+
The LED operation panel of RM6G1/RM6G1e VFDs supports external extension installation. If a standard round network cable (AMP connector) is used to connect the operation panel, it can be extended up to 100 meters, making it convenient to install the operation panel on the control box door or a remote operating location to improve the convenience of equipment operation and monitoring.
17.The motor driven by the VFD is running in the wrong direction; how to change the motor's rotation direction?+
When the running direction of the motor driven by the VFD is inconsistent with the equipment requirements, the motor's rotation direction can be adjusted through the following methods:
Before making any wiring adjustments, be sure to turn off the power and ensure equipment safety to avoid equipment damage or personal injury.
- Adjust the forward and reverse setting parameters of the VFD.
- Swap any two wires at the motor output terminal; under the premise of confirming the equipment is powered off and ensuring safety, swapping any two phases among the VFD output terminals (U, V, W) can change the motor's rotation direction.
- Check the control signal settings; if using external control terminals or PLC control, you need to check whether the forward and reverse signals are set correctly.
Before making any wiring adjustments, be sure to turn off the power and ensure equipment safety to avoid equipment damage or personal injury.
18.How to reset a VFD when an abnormal protection trips? How to clear and restart after a VFD fault?+
When a VFD has an abnormal protection (Fault), the system usually stops output to protect the equipment. At this time, you need to first check the error code displayed on the VFD to confirm the cause of the fault, such as overcurrent, overvoltage, undervoltage, or overload. After eliminating the cause of the fault, you can clear the fault state through the Reset button on the operation panel, external control terminals, or by cycling the power. After the reset is completed, restart the VFD operation. If the fault continues to occur, it is recommended to check whether the load condition, power quality, and related wiring are normal.
19.What is the cause of an OC (Overcurrent) fault in a VFD? How to resolve it?+
A VFD overcurrent is usually caused by excessive load, motor failure, too short an acceleration time, or an output short circuit. Troubleshooting methods include checking whether the load is too heavy, confirming the status of the motor and cables, extending the acceleration time, and checking whether the system wiring is normal, or further turning off the power and disconnecting the motor wires to measure the motor insulation impedance and whether the phase-to-phase impedance of the motor wires is balanced.
20.What is the cause of an OE (Overvoltage) fault in a VFD? How to resolve it?+
A VFD overvoltage often occurs when deceleration is too fast or the load inertia is too large, at which time the motor will generate regenerative energy fed back to the VFD, causing the DC bus voltage to rise. Solutions include extending the deceleration time, installing a braking resistor, or adjusting control parameters.
Additionally, the following reasons may also generate an OE error signal:
If any of the above reasons occur, please install an AC reactor at the VFD input terminal.
Additionally, the following reasons may also generate an OE error signal:
- Is there any SCR equipment near the power input terminal?
- Are there any large-capacity drive devices sharing the same power supply with the VFD? ex: (Air compressors performing start and stop actions)
- Excessive power fluctuation
- Is the deceleration time too short?
If any of the above reasons occur, please install an AC reactor at the VFD input terminal.
21.What is the cause of an LE1 (Undervoltage) fault in a VFD? How to resolve it?+
A VFD showing an LE1 low voltage (Undervoltage) fault is usually caused by the input power supply voltage being too low, excessive power fluctuations, insufficient power supply capacity, or poor contact of the power cord. When the VFD detects that the DC bus voltage is below the safe range, the system will initiate a protection mechanism to prevent equipment damage.
Troubleshooting methods include checking whether the power supply voltage is normal, confirming whether the power cords and terminal wiring are secure, and checking whether the power supply system has instantaneous voltage drops.
Troubleshooting methods include checking whether the power supply voltage is normal, confirming whether the power cords and terminal wiring are secure, and checking whether the power supply system has instantaneous voltage drops.
22.What is the cause of a GF (Ground fault) in a VFD? How to resolve it?+
When the VFD displays GF (Ground Fault), it means there may be a short to ground or leakage situation at the output terminal or motor system. Common causes include motor insulation damage, damaged motor cables, wiring errors, or a humid environment causing leakage.
Troubleshooting methods include: checking whether the motor and cable insulation is normal, confirming whether the wiring is correct, measuring the insulation resistance to ground (the motor insulation must have an impedance of more than 100Mohm at DC500V), and checking if there is moisture or pollution causing leakage. If the fault still persists, it is recommended to stop operation and have a professional technician check further.
Troubleshooting methods include: checking whether the motor and cable insulation is normal, confirming whether the wiring is correct, measuring the insulation resistance to ground (the motor insulation must have an impedance of more than 100Mohm at DC500V), and checking if there is moisture or pollution causing leakage. If the fault still persists, it is recommended to stop operation and have a professional technician check further.
23.Can an insulation withstand voltage test or insulation resistance test be performed on a VFD? What should be noted for VFD withstand voltage testing?+
It is not recommended to perform a VFD withstand voltage test or insulation resistance test yourself, because the voltage of the testing instruments is as high as 500V~2000V, and incorrect measurement methods on the VFD may cause severe damage to the VFD.
If a motor insulation resistance measurement is to be performed, the VFD and motor wires must be disconnected first, and the insulation impedance measurement must be performed solely on the motor side according to the steps in the VFD operation manual to avoid damaging the VFD.
If a motor insulation resistance measurement is to be performed, the VFD and motor wires must be disconnected first, and the insulation impedance measurement must be performed solely on the motor side according to the steps in the VFD operation manual to avoid damaging the VFD.
24.What to do if the VFD interferes with other equipment? How to reduce VFD electromagnetic interference (EMI)?+
When a VFD is operating, it generates high-frequency switching signals that may interfere with other equipment, such as PLCs, sensors, or communication equipment, through power lines or electromagnetic radiation. To reduce VFD electromagnetic interference (EMI), the following measures can be taken:
Through appropriate installation and wiring methods, VFD interference with other equipment can be effectively reduced.
- Use shielded motor cables and ground them correctly.
- Install EMI filters or reactors at the input or output terminal.
- Route power lines and control lines separately.
- Shorten motor cable length and ensure good grounding.
- Lower the VFD carrier frequency if necessary.
Through appropriate installation and wiring methods, VFD interference with other equipment can be effectively reduced.
25.Why does the 30mA earth leakage circuit breaker keep tripping when paired with a VFD? How to solve the VFD leakage circuit breaker tripping issue?+
VFDs generate high-frequency leakage currents during operation, mainly from the filter capacitors and electromagnetic interference suppression circuits on the output side of the VFD, so when using a general 30mA sensitivity earth leakage circuit breaker (RCD/ELCB), it is prone to false tripping.
Troubleshooting methods include: selecting a high-frequency tolerant or VFD-specific earth leakage circuit breaker suitable for VFDs, appropriately increasing the leakage protection current value (such as 100mA or above), confirming the grounding system is normal, and shortening the motor cable length or using shielded cables to reduce the impact of leakage current and electromagnetic interference.
Troubleshooting methods include: selecting a high-frequency tolerant or VFD-specific earth leakage circuit breaker suitable for VFDs, appropriately increasing the leakage protection current value (such as 100mA or above), confirming the grounding system is normal, and shortening the motor cable length or using shielded cables to reduce the impact of leakage current and electromagnetic interference.
26.What is the reason for the unbalanced three-phase current at the power supply terminal when the VFD is under light load?+
During light load or no-load operation, a slight unbalance in the VFD three-phase input current is usually a normal phenomenon. This is caused by the internal rectification and capacitor charge/discharge characteristics of the VFD, as well as the current fluctuations being more obvious when the load is small; as the VFD output load increases, the situation of three-phase input current unbalance will gradually narrow.
As long as the current difference is not large and the equipment operates stably, it usually does not affect system operation. But if the three-phase current difference is too large, it is recommended to check whether the input power quality, wiring status, or equipment load is normal.
As long as the current difference is not large and the equipment operates stably, it usually does not affect system operation. But if the three-phase current difference is too large, it is recommended to check whether the input power quality, wiring status, or equipment load is normal.